Description
Circular stranded hard-drawn copper phase conductor, XLPE insulated with concentrically arranged bare earth conductors.Polyethylene sheathed 600/1000 V house service connection cable. Nylon ripcord laid under sheath.
Small overall diameter - concentric construction
Lower mass - due to smaller diameter - no steel wire armour
Increased safety - reliable earthing
Improved reliability - UV stable sheath and core insulation
Tamper and vandal proof - unauthorised access to phase conductor inhibited by concentric layer
Easy strip with nylon ripcord
Applicable Standard
SANS 1507-6
Dimension Characteristics
Electrical Properties
| Cable Size (mm²) | 4 | 10 |
| Phase Conductor Resistance (Ohm/km) DC @20°C | 4.80 | 1.90 |
| Phase Core Impedance (Z) (Ohm/km) | 5.88 | 2.34 |
| Current Rating *(A) | 30 | 50 |
| Symmetrical Short Circuit Rating for 1s in kA | 0.572 | 1.431 |
*Note: - In air, with 30 °C ambient with maximum conductor temperature 90 °C
Mechanical Properties
| Cable Size (mm²) | 4 | 10 |
| Phase Conductor (No. X OD) (mm) | 7 x 0.92 | 7 x 1.45 |
| Nominal Insulation Thickness (mm) | 1.0 | 1.0 |
| Earth Size (mm²) | 4 | 10 |
| Earth Conductor (No. X OD) (mm) | 8 x 0.85 | 18 x 0.85 |
| Nominal Sheath Thickness (mm) | 1.4 | 1.4 |
| Approximate Cable OD (mm) | 9.0 | 11.0 |
| Approximate Cable Mass (kg/km) | 121 | 249 |